103
Displayed fault
code
System characteristics Cause Measures
F.548 Mixer closes. Heating circuit
pump is operational.
Short circuit, flow temper-
ature sensor for heating
circuit 4 with mixer
Check flow temperature sensor,
mixer 4.
Measure voltage at sensor input
on electronics module. Set value:
3.3 V with sensor disconnected.
Check commissioning assistant
setting.
Checking setting of ADIO rotary
switch.
F.549 Mixer closes. Heating circuit
pump is operational.
Short circuit, flow temper-
ature sensor for heating
circuit 4 with mixer
Check flow temperature sensor,
mixer 4.
Measure voltage at sensor input on
electronics module. Set value:
3.3 V
with sensor disconnected.
Note
If subscriber faults occur, "Fault, subscriber ..." is dis-
played.
Repairs
!
Please note
Residual water will escape when the boiler or
one of the following components is fitted or
removed:
Water-filled pipework
Heat exchanger
Circulation pumps
Plate heat exchanger
Components fitted in the heating water or
DHW circuit.
Water ingress can result in damage to other
components.
Protect the following components against
ingress of water:
Control unit components (especially in the
service position)
Electrical components
Plug-in connections
Cables and leads
Shutting down the boiler
1. Switch OFF the power supply.
2. Shut off the gas supply.
3. If the boiler needs to be removed:
Disconnect the balanced flue system.
Drain the boiler on the heating water and DHW
sides.
Disconnect the on-site cables/leads.
Troubleshooting
Fault messages (cont.)
5593201