41
Fig. 29
Affix a label in the operating instructions.
Calling up the commissioning assistant at a later
point
If you need to continue commissioning later, the com-
missioning assistant can be reactivated at any time.
Tap the following buttons:
1.
2. "Service"
3. Enter password "viservice".
4. Use to confirm.
5. "Commissioning"
Filling the heating system
Fill water
According to EN 1717 with DIN 1988-100, as a heat
transfer medium for DHW heating, the heating water
must meet fluid category ≤ 3. This requirement is met if
water of potable quality is used as heating water. For
example, if additives are used, the additive manufac-
turer must specify which category the treated heating
water comes under.
!
Please note
Unsuitable fill water increases the level of
deposits and corrosion and may lead to appli-
ance damage.
■
Flush the heating system thoroughly before
filling.
■
Only use fill water of potable water quality.
■
Special antifreeze suitable for heating systems
can be added to the fill water. The antifreeze
manufacturer must verify its suitability.
■
Fill and top-up water with a water hardness in
excess of the following values must be soft-
ened, e.g. with a small softening system for
heating water.
Total permissible hardness of the fill and top-up water
Total heating output Specific system volume
kW < 20 l/kW ≥ 20 l/kW to < 50 l/kW ≥ 50 l/kW
≤ 50
≤ 3.0 mol/m
3
(16.8 °dH) ≤ 2.0 mol/m
3
(11.2 °dH) < 0.02 mol/m
3
(0.11 °dH)
> 50 to ≤ 200
≤ 2.0 mol/m
3
(11.2 °dH) ≤ 1.5 mol/m
3
(8.4 °dH) < 0.02 mol/m
3
(0.11 °dH)
> 200 to ≤ 600
≤ 1.5 mol/m
3
(8.4 °dH) ≤ 0.02 mol/m
3
(0.11 °dH) < 0.02 mol/m
3
(0.11 °dH)
> 600
< 0.02 mol/m
3
(0.11 °dH) < 0.02 mol/m
3
(0.11 °dH) < 0.02 mol/m
3
(0.11 °dH)
Commissioning, inspection, maintenance
Commissioning the system with the commissioning… (cont.)