76
1397.1 "Heating limit: Economy function, outside temperature, heating circuit 3"
Setting Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25 °C 25 Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35 Heating limit adjustable from 10 to 35 °C in 1 °C incre-
ments
Solar
Note
Parameter values in bold are factory settings.
950.0 "Flow rate, solar circuit at max. pump speed"
Setting Explanations
7.0 l/min 7 Required for calculating the solar yield
0.1 to 25.5 l/min 0.1 to 25.5 Flow rate adjustable from 0.1 to 25.5 l/min
1 step ≙ 0.1 l/min
1118.0 "Min. speed, solar circuit pump"
Setting Explanations
23 Minimum speed of solar circuit pump in %
0 to 100 Speed adjustable from 0 to 100 %
1118.1 "Max. speed, solar circuit pump"
Setting Explanations
84 Minimum speed of solar circuit pump in %
0 to 100 Speed adjustable from 0 to 100 %
1125.0 "Maximum cylinder temperature for solar DHW heating"
Setting Explanations
Maximum temperature for solar heating of storage
medium
60 °C 60 Factory setting: Set value 60 °C
10 to 90 Set value adjustable from 10 to 90 °C
!
Please note
A high set value may incur a risk of scalding at
the draw-off points.
If required, take on-site action and inform the
system user.