71
Note
Parameter values in bold are factory settings.
424.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 1"
Setting Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K 0 Delivered condition increase 0 K
0 to 20 Temperature rise adjustable from 0 to 20 K
424.4 "Duration for set flow temperature increase, heating circuit 1"
Setting Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60 min 60 Delivered condition 60 min
0 to 120 Temperature rise adjustable from 0 to 120 min
426.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 2"
Setting Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K 0 Delivered condition increase 0 K
0 to 20 Temperature rise adjustable from 0 to 20 K
426.4 "Duration for set flow temperature increase, heating circuit 2"
Setting Explanations
Duration for set flow temperature increase
See also chapter "Function description"
60 min 60 Delivered condition 60 min
0 to 120 Temperature rise adjustable from 0 to 120 min
428.3 "Set flow temperature increased when switching from operation with reduced room temperature to
operation with standard/comfort room temperature, heating circuit 3"
Setting Explanations
Set flow temperature increased when changing from
operation at reduced room temperature to operation at
standard room temperature or comfort room tempera-
ture.
See also chapter "Function description"
0 K 0 Delivered condition increase 0 K
0 to 20 Temperature rise adjustable from 0 to 20 K
System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating circuit 3, Heating circuit 4
5593201