74
935.6 "Operating mode of heating circuit 3"
Setting Explanations
Heating mode:
Weather-compensated without room tem-
perature hook-up
4 Weather-compensated without room temperature in-
fluence
Weather-compensated with room tempera-
ture hook-up
7 Weather-compensated with room temperature influ-
ence
See also parameter 935.7
935.7 "Room influence factor, heating circuit 3"
Setting Explanations
The higher the value, the greater the influence of the
room temperature on the set flow temperature of the
heating circuit (heating curve). Operation with room
temperature hook-up must be set for the heating cir-
cuit (parameter 935.6). Change value for heating cir-
cuit with mixer only.
For a sample calculation, see chapter "Heating curve"
in the "Function description"
8 Room influence factor
0 to 64 Room influence adjustable from 0 to 64
1102.0 "Min. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting Explanations
Minimum speed of the internal circulation pump in
heating mode with standard room temperature
... Delivered condition specified by settings specific to
the heat generator
0 to 100 Minimum speed adjustable from 0 to 100 %
1102.1 "Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting Explanations
Maximum speed of the internal circulation pump in
heating mode with standard room temperature
... Delivered condition specified by settings specific to
the heat generator
0 to 100 Maximum speed adjustable from 0 to 100 %
1192.0 "Minimum flow temperature limit, heating circuit 1"
Setting Explanations
Minimum flow temperature limit for the heating circuit
20 °C 20 Minimum limit in the delivered condition 20 °C
1 to 90 Setting range limited by heat generator-specific pa-
rameters
1192.1 "Maximum flow temperature limit, heating circuit 1"
Setting Explanations
Maximum flow temperature limit for the heating circuit
74 °C 74 Maximum limit in the delivered condition 74 °C
10 to 100 Setting range limited by heat generator-specific pa-
rameters
System configuration (parameters)
Heating circuit 1, Heating circuit 2, Heating… (cont.)