Displayed fault
code
System characteristics Cause Measures
F.346 Burner in a fault state Ionisation current calibra-
tion error
Check the gas supply pressure.
Check gas solenoid valve strain-
er on the inlet side for contami-
nation.
Check ionisation electrode for
contamination.
Check flue system. Remove flue
gas recirculation if required.
Check the connecting cable to
the fan unit.
Check impeller for ease of opera-
tion.
Reset the appliance.
F.348 Burner in a fault state Gas modulation valve If several heat generators are con-
nected to a common flue system:
Check whether "Multiple connec-
tions" is set in the commissioning
assistant.
Check the flue system for unre-
stricted flow.
If fault remains, replace gas fan
unit.
F.349 Burner in a fault state Air mass rate flow not de-
tected correctly in fan unit.
Check for dust contamination in
the supply air.
Check burner gauze assembly
for contamination.
Reset the appliance. If the fault oc-
curs repeatedly, replace the gas
fan unit.
F.350, F.351 Burner in a fault state Ionisation current lies out-
side the permissible range
Replace BCU burner control unit
(see page 109).
F.352 Burner in a fault state CO limit within appliance
exceeded
Check entire flue gas path for the
following:
Flue gas recirculation
Leaks
Flue gas back pressure caused
by water pocket (if flue system
fall is insufficient)
Constrictions
Blockages
Repair flue system if necessary.
Reset the appliance.
F.353 Burner shutdown with restart
if demand exists
Insufficient gas supply,
burner output reduced
Check the gas supply.
Optically check input-side screen
in the gas solenoid valve for con-
tamination.
Reset the appliance.
F.354 Burner in a fault state Gas modulation valve tol-
erance outside permissi-
ble range
Replace gas fan unit.
F.355 Burner in a fault state Analogue signal reference
check: Flame signal is al-
ready present at burner
start.
Replace BCU burner control unit
(see page 109).
Troubleshooting
Fault messages (cont.)
5593201