38
SIM card faults
Field strength
indicator "2"
Indicator for
mobile net-
work connec-
tion status
"3"
Operating
status indica-
tor "4"
Type of fault and measures
Flashes red Off Flashes red
quickly
SIM card missing or faulty.
or
Insufficient field strength.
Insert SIM card (see page 24).
or
Adjust the aerial.
Flashes yellow Flashes yel-
low
Flashes red
quickly
PIN entry required.
Enter PIN (see page 27).
Illuminates red Off Flashes red
quickly
PUK entry required.
Enter PUK (see page 28).
Faults without LED indication
Fault Measures
All indicators on the Vitocom 100 are off. Check the Vitocom 100 power supply.
Fault messages
Fault messages for the heating system
are shown on the control unit display.
These fault messages contain a fault
message text and a fault message
code.
Contact your heating contractor in con-
nection with each fault message
received.
The SMS sent by the Vitocom 100 shows
the fault message in a similar way using
the following information elements:
Operating state of the system after the
fault occurred, e.g. "emergency mode"
Cause of fault, e.g. "outside tempera-
ture sensor"
Display of the fault code for the precise
cause of the fault by means of the last
two characters in the SMS text (e.g.
"10")
What to do if...