For the on-line access to the Ethernet PG/OP channel you have to assign
IP address parameters by means of the "initialization".
After allocation the Ethernet PG/OP canal may be accessed by the IP
address parameters.
In the following the steps of initialization are described. More information
may be found at "initialization" of the PG/OP channel.
• Determine the Ethernet (MAC) address of the Ethernet PG/OP channel.
This always may be found as 1
st
address under the front flap of the CPU
on a sticker on the left side.
Ethernet address
Ethernet PG/OP
• Establish a network connection between Ethernet PG/OP channel of the
CPU and PC.
• Set at Siemens SIMATIC manager via Options > Set PG/PC Interface
the access path to "TCP/IP -> Network card .... Protocol RFC 1006".
• Open with PLC > Assign Ethernet Address the dialog window for
"initialization" of a station.
• Determine the CPU components via MAC address and assign it to IP
address parameters. As long as the Ethernet PG/OP channel was not
initialized yet, this owns the IP address 0.0.0.0 and the station name
"Onboard PG/OP".
Direct after the assignment the Ethernet PG/OP channel may be reached
by the Siemens SIMATIC manager by means of these IP address
parameters.
The transfer happens in the following approach:
• Open your project in the Siemens SIMATIC manager.
• Set at Siemens SIMATIC manager via Options > Set PG/PC Interface
the access path to "TCP/IP -> Network card .... Protocol RFC 1006".
• Click to PLC > Download → the dialog "Select target module" is opened.
Select your target module and enter the IP address parameters of the
Ethernet PG/OP channel as address for connection. Provided that no
new hardware configuration is transferred to the CPU, the given
Ethernet-PG/OP channel is permanently stored in the project as transfer
channel.
• With [OK] the transfer is started. System dependent you get a message
that the projected system differs from target system. This message may
be accepted by [OK] → your project is transferred and may be executed
in the CPU after transfer.
Transfer via Ether-
net PG/OP channel
(initialization
necessary)
Initialization
Transfer