Manual VIPA System 300V Chapter 6 Deployment CPU 31x with TCP/IP
HB130E - CPU - Rev. 11/50 6-13
Hardware configuration
Precondition: SIMATIC manager from Siemens V. 5.1 or V.5.2 with SP1
and SIMATIC NET
• Start the SIMATIC manager from Siemens with a new project.
• Add a new System300 station via Insert > Station > SIMATIC 300-
Station.
• Activate the station "SIMATIC 300" and open the hardware configurator
by clicking on "Hardware".
• Configure a rack (Simatic300 > Rack-300 > Profile rail).
• For all CPUs 31x from VIPA are configured as CPU 315-2DP, you select
the CPU 315-2DP with the order no. 6ES7 315-2AF03-0AB0 in the
hardware catalog.
This is to find under Simatic300 > CPU-300 > CPU 315-2 DP.
• Place your modules starting at plug-in location 4. After that place your
virtual CP343-1 TCP(Simatic300 > CP-300 > Industrial Ethernet > CP
343-1 TCP).
• If needed parameterize the CPU res. the modules. The parameter
window is opened at double click on the depending module.
• Via a double click on the CP 343-1 TCP you open the properties window
and you type that IP address and that Subnet mask into properties that
you have defined in WinNCS.
• Save your project.
The transfer of the hardware configuration happens together with the user
application.
User application
• Create a communication channel between CPU and CP by means of the
SYNCHRON block.
• Program the according SEND and RECEIVE blocks for initializing send
and receive orders.
• Program the blocks SEND_ALL res. RECV_ALL for data transfer.
Transfer of user application and hardware configuration
To transfer your user application and the hardware configuration you have
the following possibilities:
• Transfer via MPI respectively Profibus
• Transfer via MMC
• Transfer via Ethernet
Details about project transfer can be found at chapter "Deployment CPU
31x" at "Project transfer".
Here the fast introduction ends. The following pages contain a detailed
description of the project engineering.
... continue
fast introduction