5. PROGRAMMING
38
D-304762 PowerMaster-10/30 G2 Installer's Guide
Option Configuration Instructions
CP-01 features not to be enabled in UL Listed product.
4. To comply with EN requirements, the entry delay must not exceed 45 sec.
03:EXIT DELAY
This option allows programming the time length of the exit delay. An exit delay allows the user
to arm the system and leave the protected site via specific routes and exit/entry doors without
causing an alarm. Slow-rate warning beeps start sounding once the arming command has
been given, until the last 10 seconds of the delay, during which the beeping rate increases.
Options: 30 sec.; 60 sec. (default); 90 sec.; 120 sec., 3 min. and 4 min.
Notes:
1. To comply with UL requirements, do not set to 3 min or 4 min.
2. To comply with CP-01 requirements, the "30s" delay must not be used. CP-01
features not to be enabled in UL Listed product.
04:EXIT MODE
The "Exit Delay" time can be further adjusted according to your preferred exit route.
The control panel provides you with the following "Exit Mode" options:
A: "normal" - The exit delay is exactly as defined.
B: “restrt+arm home” - Exit delay restarts when the door is reopened during exit delay. If no
door was opened during exit delay "AWAY", the control panel will be armed "HOME".
C: "restart>reentry" - The exit delay restarts when the door is reopened during exit delay.
The restart occurs once only. Restarting the exit delay is helpful if the user re-enters
immediately after going out to retrieve an item that he left behind.
D: "end by exit" - The exit delay expires (ends) automatically when the exit door is closed
even if the defined exit delay time was not completed.
Options: normal (default); restrt+arm home; restart>reentry and end by exit.
Note: In some PowerMaster variants, this menu is displayed in the Operation Mode only (see
section 5.15.
05:QUICK ARM
Define whether or not the user will be allowed to perform quick arming or not. Once quick
arming is permitted, the control panel does not request a user code before it arms the system.
Options: OFF (default) and ON (default in USA).
06:BYPASS ARM
Define whether or not the user will be allowed to manually bypass individual zones, or allow
the system to perform automatic bypassing of open zones during the exit delay (i.e.
"force arm"). If a zone is open and "forced arming" is not permitted, the system cannot be
armed and “NOT READY” is displayed. If "no bypass" is selected, neither manual bypassing
nor force arming is allowed which means that all zones must be secured before arming.
Options: no bypass (default); force arm and manual bypass (default in USA).
Notes:
1. To comply with EN requirements, "manual bypass" must be selected.
2. The option "force arm" is not applicable in the UK.
3. "force arm" or "automatic bypass" feature is not allowed in UL installations; only
"manual bypass" must be enabled. For manual bypass, audible trouble may be
silenced.
4. A zone in Soak Test
1
mode that is configured as bypass will trigger a test fail
event if the system detects a potential alarm event.
5. There is no limit of reported events when a bypass zone is in Soak Test
1
mode.
07:LATCHKEY ARM
When "ON", a “latchkey” message will be reported by voice
2
or SMS message to users (see
Note) upon disarming by a “latchkey user” (users 5-8 or keyfob transmitters 5-8 in PowerMaster-
10 G2 system / users 23-32 or keyfob transmitters 23-32 in PowerMaster-30 G2 system). This
mode is useful when parents at work want to be informed of a child’s return from school.
Options: OFF (default) and ON.
Notes:
To enable the reporting, you must configure the system to report "alrt" events to Private users
(Latchkey belongs to the "alerts" group of events). Refer to section 5.6.4 "REPORTED
EVENTS" option in both "
VOICE REPORT
" & "
SMS REPORT
" menus.
Latchkey Arming is supplemental in UL installations.
08:DISARM OPTION
Certain regulations require that when the system is armed in AWAY mode, it may not be
disarmed from the outside of the house (such as by keyfobs) before entering the protected
1
Soak Test is not applicable for UL installations.
2
Refers to PowerMaster-30 G2 with voice option only