Active if Output 3 (Output 3
Menu) is [``AL] (Alarm),
Alarm Sides 3 (Output 3 Menu)
is not [hi``], or Output 3 is
present (97 _ _-_ _ D _-_ _ _ _)
and Operations Page Mode
(Lockout Menu) is not set to
[hide]
.
340 r/wProcess: low
limit of
selected
sensor
range
Process: low limit of
selected sensor range
to Alarm 3 High -1
[A3Lo] Alarm 3 Low
Sets the low alarm
set point for output
3.
Active if Output 2 (Output 2
Menu) is set to [``AL] (Alarm),
Alarm Active Sides 2 (Output 2
Menu) is not set to [Lo``],
Output 2 is present (97 _ _-_ D
_ _-_ _ _ _ or 97 _ _-_ K_ _-_ _ _
_) and Operations Page Mode
(Lockout Menu) is not set to
[hide].
322 r/wProcess: high
limit of
selected
sensor
range
Process:
Alarm 2 Low +1 to
high limit of selected
sensor range
[A2hi] Alarm 2 High
Sets the high alarm
set point for output
2.
Active if Output 2 (Output 2
Menu) is set to [``AL] (Alarm),
Alarm Active Sides 2 (Output 2
Menu) is not set to [hi``],
Output 2 is present (97 _ _-_ D
_ _-_ _ _ _ or 97 _ _-_ K_ _-_ _ _
_) and Operations Page Mode
(Lockout Menu) is not set to
[hide].
321 r/wProcess: low
limit of
selected
sensor
range
Process: low limit of
selected sensor range
to Alarm 2 High -1
[A2Lo] Alarm 2 Low
Sets the low alarm
set point for output
2.
[Alm] Alarm Menu
[Oper] Operations Page
Active: Always615 r/w0-1999 to 9999
[CAL1] Calibration Offset
Sets the input 1
calibration offset.
Active: Always702 r/w
[`rh1][L`Lo] +1 to [`rh1][L`hi] High Limit Set
Point
Sets the high limit
point.
Active: Always701 r/w
[`rL1][`rL1] to [L`hi] -1[L`Lo] Low Limit Set
Point
Sets the low limit
point.
[LIM] Limit Menu
[Oper] Operations Page
Watlow Series 97 Parameters ■ 6.5
Operations Page / Alarm and Limit Menus
Display Parameter Range Default Modbus Conditions for
Address Parameters to Appear
read/write
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.