Watlow 97 series - Page 53

Watlow 97 series
89 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Active if Output 4 is equipped for
communications (96 _ _-_ _ _ R-
_ _ _ _ or 96 _ _-_ _ _ U-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
none*
[9600][1200] 1200
[2400] 2400
[4800] 4800
[9600] 9600
[1(20] 19.2K
[bAUd] Baud Rate
Sets
communications
baud rate.
Active if Output 4 is retransmit
(97 _ _-_ _ _ M-_ _ _ _), and
Analog Output 4 (Output 4
Menu) is set to [`yes] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none*0
-1999 to 9999
[ACAL] Analog Output
Offset
Sets analog output
offset.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _),
and Analog Output 4 (Output 4
Menu) is set to [`yes] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none*999Analog Range Low to
9999
[A`hi] Analog Output
High
Sets analog output
range high scaling.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _),
and Analog Output 4 (Output 4
Menu) is set to [Proc] and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none*-999-1999 to Analog Range
High
[A`Lo] Analog Output
Low
Sets analog output
range low scaling.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
none*
[4-20][4-20] 4-20 mA
[0-20] 0-20 mA
[0-`5] 0-5VÎ (dc)
[1-`5] 1-5VÎ (dc)
[0-10] 0-10VÎ (dc)
[Prc4] Process 4 Type
Sets process 4 out-
put type.
Active if Output 4 is equipped for
retransmit (97 _ _-_ _ _ M-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to [hide].
none*
[proc][``no] not active
[proc] process
[Aout] Analog Output 4
Selects output 4
retransmit signal.
Active if Output 4 is equipped for
a relay (97 _ _-_ _ _ D-_ _ _ _),
Output 4 is Set to [``AL]
(Alarm) and Setup Page Lock
(Lockout Menu) is not set to
[hide].
none*
[`yes][``no] no
[`Yes] yes
[Anu4] Alarm
Annunciation 4
Selects alarm 4
annunciation option.
Active if Output 4 is equipped for
a relay (97 _ _-_ _ _ D-_ _ _ _),
Output 4 (Output 4 Menu) is
set to [``AL] (Alarm) and
Setup Page Lock (Lockout
Menu) is not set to [hide].
none*
[al`0][al`0] alarm condition
de-energizes output
[al`C] alarm condition
energizes output
[Lgc4] Alarm Logic 4
Selects alarm 4
output condition in
alarm state.
Watlow Series 97 Parameters 6.13
Setup Page / Output 4 Menu
Display Parameter Range Default Modbus Conditions for
Address Parameters to Appear
read/write
NOTE: For more information about how parameter seetings affect the controller’s operation, see Chapter Five, Features.
*Output 4 parameters cannot
be changed with the Modbus
interface.