ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 107 of 140
Htr Addr 52:
Point Name
BACnet
Address
Lon Name
Lon SNVT
Modbus
Reg. Type
Modbus Data
Address
SP Outlet
AV: 3700
nvoSPHTR_52_1
SNVT_count_inc
Input
33700
SP Valve Position
AV: 3701
nvoSPHTR_52_2
SNVT_count_inc
Input
33701
SP Setpoint
AV: 3702
nvoSPHTR_52_3
SNVT_count_inc
Input
33702
SP Error #
AV: 3703
nvoSPHTR_52_4
SNVT_count_inc
Input
33703
SP Delta Pres
AV: 3704
nvoSPHTR_52_5
SNVT_count_inc
Input
33704
SP DHW Inlet
AV: 3705
nvoSPHTR_52_6
SNVT_count_inc
Input
33705
SP Flow
AV: 3706
nvoSPHTR_52_7
SNVT_count_inc
Input
33706
SP Boiler Inlet
AV: 3707
nvoSPHTR_52_8
SNVT_count_inc
Input
33707
Htr Addr 53:
Point Name
BACnet
Address
Lon Name
Lon SNVT
Modbus
Reg. Type
Modbus
Data
Address
SP Outlet
AV: 3800
nvoSPHTR_53_1
SNVT_count_inc
Input
33800
SP Valve Position
AV: 3801
nvoSPHTR_53_2
SNVT_count_inc
Input
33801
SP Setpoint
AV: 3802
nvoSPHTR_53_3
SNVT_count_inc
Input
33802
SP Error #
AV: 3803
nvoSPHTR_53_4
SNVT_count_inc
Input
33803
SP Delta Pres
AV: 3804
nvoSPHTR_53_5
SNVT_count_inc
Input
33804
SP DHW Inlet
AV: 3805
nvoSPHTR_53_6
SNVT_count_inc
Input
33805
SP Flow
AV: 3806
nvoSPHTR_53_7
SNVT_count_inc
Input
33806
SP Boiler Inlet
AV: 3807
nvoSPHTR_53_8
SNVT_count_inc
Input
33807