ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX C: AERCO EQUIPMENT POINT MAPPINGS
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 81 of 140
Appendix C-7: MFC LMV5 Points
Point Name
FPC-N34
FPC-N35
Modbus
Address
BACnet
Data Type
BACnet
Object Id
N2 Data
Type
N2 Point
Address
Lon Name
Lon SNVT Type
Phase
AI
1
AI
1
nvoPhase_XXX
SNVT_count_inc_f
40001
Pos of curr act fuel act
AI
2
AI
2
nvoPosCrAcFl_XXX
SNVT_count_inc_f
40002
Pos of gas actuator
AI
3
AI
3
nvoPosGasAct_XXX
SNVT_count_inc_f
40003
Pos of oil actuator
AI
4
AI
4
nvoPosOilAct_XXX
SNVT_count_inc_f
40004
Pos of air actuator
AI
5
AI
5
nvoPosAirAct_XXX
SNVT_count_inc_f
40005
Pos of aux actuator 1
AI
6
AI
6
nvoPosAuxAc1_XXX
SNVT_count_inc_f
40006
Pos of aux actuator 2
AI
7
AI
7
nvoPosAuxAc2_XXX
SNVT_count_inc_f
40007
Pos of aux actuator 3
AI
8
AI
8
nvoPosAuxAc3_XXX
SNVT_count_inc_f
40008
Manipulated variable for VSD
AI
9
AI
9
nvoManVarVSD_XXX
SNVT_lev_percent
40009
Current type of fuel
AI
10
AI
10
nvoCurTypFl_XXX
SNVT_count_inc_f
40010
Current output
AI
11
AI
11
nvoCurOutput_XXX
SNVT_lev_percent
40011
Current setpoint/temp/press
AI
12
AI
12
nvoCurSP_Tmp_XXX
SNVT_count_inc_f
40012
Actual value/temp/press
AI
13
AI
13
nvoActVal_Tp_XXX
SNVT_count_inc_f
40013
Flame signal
AI
14
AI
14
nvoFlameSig_XXX
SNVT_lev_percent
40014
Current fuel throughput
AI
15
AI
15
nvoCurFlThr_XXX
SNVT_count_inc_f
40015
Current O2 value
AI
16
AI
16
nvoCurO2Val_XXX
SNVT_lev_percent
40016
Volume unit of gas
AI
17
AI
17
nvoVolGsUnit_XXX
SNVT_count_inc_f
40017
Volume unit of oil
AI
18
AI
18
nvoVolOlUnit_XXX
SNVT_count_inc_f
40018
Unit of temp
AI
19
AI
19
nvoUnitTemp_XXX
SNVT_count_inc_f
40019
Unit of press
AI
20
AI
20
nvoUnitPress_XXX
SNVT_count_inc_f
40020
Sensor selection
AI
21
AI
21
nvoSensorSel_XXX
SNVT_count_inc_f
40021
Startup counter total
AI
22
AI
22
nvoStrtCnToT_XXX
SNVT_count_inc_f
40022, 40022
Hours run counter
AI
23
AI
23
nvoHrsRunCnt_XXX
SNVT_count_inc_f
40024, 40025
Current error: Error code
AI
24
AI
24
nvoErrCode_XXX
SNVT_count_inc_f
40026
Current error: Diag code
AI
25
AI
25
nvoDiagCode_XXX
SNVT_count_inc_f
40027
Current error: Error class
AI
26
AI
26
nvoErrClass_XXX
SNVT_count_inc_f
40028
Current error: Error phase
AI
27
AI
27
nvoErrPhase_XXX
SNVT_count_inc_f
40029
Temp limiter OFF threshold
AI
28
AI
28
nvoTmpLmOfTh_XXX
SNVT_count_inc_f
40030
Supply air temp
AI
29
AI
29
nvoSupAirTmp_XXX
SNVT_count_inc_f
40031