ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX C: AERCO EQUIPMENT POINT MAPPINGS
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 89 of 140
Standalone SmartPlate EV Points:
Point Name
BACnet
Address
Lon Name
Lon SNVT
Modbus
Reg
Type
Modbus
Data
Address
DHW Out
AV: 1
nvoSPEVDhwOut_XXX
SNVT_count_inc
Input
1
Setpoint
AV: 2
nviSPEVSetpoint_XXX
SNVT_count_inc
Holding
2
Valve POS
AV: 4
nvoSPEVValvePOS_XXX
SNVT_count_inc
Input
4
DHW Flow
AV: 364
nvoSPEVDhwFlow_XXX
SNVT_count_inc
Input
364
BW Inlet T
AV: 370
nvoSPEVBWInlet_T_XXX
SNVT_count_inc
Input
370
DHW Inlet T
AV: 373
nvoSPEVDhwInlet_T_XXX
SNVT_count_inc
Input
373
DP
AV: 379
nvoSPEVDP_XXX
SNVT_count_inc
Input
379
Alarm 1 Out
AV: 10249
nvoSPEVAlarm1Out_XXX
SNVT_count_f
Input
10249
Alarm 2 Out
AV: 10265
nvoSPEVAlarm2Out_XXX
SNVT_count_f
Input
10265
Alarm 3 Out
AV: 10281
nvoSPEVAlarm3Out_XXX
SNVT_count_f
Input
10281
Alarm 4 Out
AV: 10297
nvoSPEVAlarm4Out_XXX
SNVT_count_f
Input
10297
Alarm 5 Out
AV: 10313
nvoSPEVAlarm5Out_XXX
SNVT_count_f
Input
10313
Alarm 6 Out
AV: 10329
nvoSPEVAlarm6Out_XXX
SNVT_count_f
Input
10329
Alarm 7 Out
AV: 10345
nvoSPEVAlarm7Out_XXX
SNVT_count_f
Input
10345
Alarm 8 Out
AV: 10361
nvoSPEVAlarm8Out_XXX
SNVT_count_f
Input
10361

Table of Contents