ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX C: AERCO EQUIPMENT POINT MAPPINGS
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 77 of 140
Appendix C-3: C-More Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus TCP/IP and LonWorks
Appendix C-3: C-More Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus TCP/IP and LonWorks
Name
Point Name
BACnet
Object
Type
BACnet
Object
ID
N2
Data
Type
N2 Point
Address
Lon Name
Lon SNVT
Modbus
Address
Fire Rate Out
boilerstate_XXX
AV
1
ADF
1
nvoBlrState_XXX
SNVT_count_inc
30009
Active Setpoint
effectsetpt_XXX
AV
2
ADF
2
nvoEffSetpt_XXX
SNVT_count_inc
30017
Net Remote Setpoint
setpt_XXX
AV
3
ADF
3
nviSetpt_XXX
SNVT_count_inc
40001
Net Direct Drive
boilercmd_XXX
AV
4
ADF
4
nviBlrCmd_XXX
SNVT_count_inc
40002
Fire Rate In
boilerload_XXX
AV
5
ADF
5
nvoBlrLoad_XXX
SNVT_count_inc
30018
Outlet Temp
localsuptemp_XXX
AV
6
ADF
6
nvoLocSupTmp_XXX
SNVT_count_inc
30003
Display Code
dispcode_XXX
AV
7
ADF
7
nvoDispCode_XXX
SNVT_count_inc
30001
Unit Status
unitstat_XXX
AV
8
ADF
8
nvoUnitStat_XXX
SNVT_count_inc
30002
Run Cycles
runcycles_XXX
AV
9
ADF
9
nvoRunCycles_XXX
SNVT_count_f
30012,
30013
Run Hours
runhours_XXX
AV
10
ADF
10
nvoRunHours_XXX
SNVT_count_f
30014,
30015
Oxygen Level
o2level_XXX
AV
11
ADF
11
nvoO2Lev_XXX
SNVT_count_inc
30010
Exhaust Temp
exhtemp_XXX
AV
12
ADF
12
nvoLocExhTmp_XXX
SNVT_count_inc
30007
Appendix C-4: Modulex Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus TCP/IP and LonWorks
Appendix C-4: Modulex Modbus RTU Mappings to BACnet MS/TP, BACnet/IP, Metasys N2, Modbus TCP/IP and LonWorks
Name
Point Name
BACnet
Object
Type
BACnet
Object
ID
N2
Data
Type
N2 Point
Address
Lon Name
Lon SNVT
Modbus
Address
Actual Modulation
Level
boilerstate_XXX
AV
1
ADF
1
nvoMlxState_XXX
SNVT_count_inc
41009
Target Setpoint
effectsetpt_XXX
AV
2
ADF
2
nvoMlxSetpt_XXX
SNVT_count_inc
41019
Requested Outlet
Temp
setpt_XXX
AV
3
ADF
3
nviMlxSPRq_XXX
SNVT_count_inc
41005
Net Direct Drive
boilercmd_XXX
AV
4
ADF
4
nviMlxCmd_XXX
SNVT_count_inc
40002