ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX F: C-MORE STATUS AND FAULT MESSAGES
OMM-0150_B • 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 118 of 140
Appendix F: C-More Status and Fault Messages
The SSOV switch opened during purge.
PRG SWTCH OPEN
DURING PURGE
The Purge Position Limit switch on the Air/Fuel valve
opened during purge.
IGN SWTCH OPEN
DURING IGNITION
The Ignition Position Limit switch on the Air/Fuel valve
opened during ignition.
The Blower Proof Switch opened during ignition.
The Blower Proof Switch opened during run.
The SSOV switch closed or failed to open during ignition.
The SSOV switch closed for more than 15 seconds
during run.
The Flame signal was not seen during ignition or lost
within 5 seconds after ignition.
The Flame signal was lost during run.
The High Exhaust Temperature Limit Switch is closed.
A power loss occurred. The time and date when power
was restored is displayed.
A failure has been detected in one of the relays that control
the SSOV.
The Flame signal was seen for more than 60 seconds
during standby.
The Heat Demand Relays on the Ignition board failed to
activate when commanded.
IGN SWTCH CLOSED
DURING PURGE
The Ignition Position Limit switch on the Air/Fuel valve
closed during purge.