ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX B: EQUIPMENT MONITOR AND CONTROL POINT DEFINITIONS
OMM-0150_B • 5/20/2021 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 58 of 140
Appendix B-1: AERCO C-More & ACS/BMS II/BMS Point Definitions
GF-108, GF-
124, GF-114
Point Name
Modbus Data
Address
(Hex/Dec.)
Bit (0 to 65535)
Bit 0 = Outside Air Sensor
Error
Bit 1 = Header Sensor Error
Bit 2 = Interlock 1 Error
Bit 3 = Interlock 2 Error
Bit 4 = Indoor Air/Return Sens
Error
Bit 5 = 4-20 mA Input Error
(0 to 40) BMS
(0 to 32) BMSII, ACS
(0 to 40) BMS
(0 to 32) BMSII, ACS
(1 to 40) BMS
(1 to 32) BMSII, ACS
Boiler 1 Status
(PWM Boiler 1)
Enum (1 to 40, 119, 120)
1 to 40 = Fired and Sequence
119 = Not On Line
120 = On Line But Not Fired
Boiler 2 Status
(PWM Boiler 2)
Boiler 3 Status
(PWM Boiler 3)
Boiler 4 Status
(PWM Boiler 4)
Boiler 5 Status
(PWM Boiler 5)
Boiler 6 Status
(PWM Boiler 6)
Boiler 7 Status
(PWM Boiler 7)
Boiler 8 Status
(PWM Boiler 8)
Enum (1 to 40, 119, 120)
1 to 40 = Fired and Sequence
119 = Not On Line
120 = On Line But Not Fired
121 = On Line But Disabled
122 = On Line But Faulted