ProtoNode FPC-N34 & FPC-N35 User Manual
APPENDIX D: EIGHT C-MORE BOILERS/HEATERS AND BST/WHM MASTER
OMM-0150_B 5/20/2021 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 98 of 140
Appendix D: Eight C-More Boilers/Heaters and BST/WHM Master
Equip
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon NAME
Lon SNVT
Lon Direction
Modbus
Address
9
Run Cycles Lower
SMD_BAS_IP_HTR_09_[16]
AV:1116
Data Float
222
nvoHTR_09_17
inc count (9)
Output (non-polled)
31116
9
Run Hours Upper
SMD_BAS_IP_HTR_09_[17]
AV:1117
Data Float
223
nvoHTR_09_18
inc count (9)
Output (non-polled)
31117
9
Run Hours Lower
SMD_BAS_IP_HTR_09_[18]
AV:1118
Data Float
224
nvoHTR_09_19
inc count (9)
Output (non-polled)
31118
9
Oxygen Level
SMD_BAS_IP_HTR_09_[19]
AV:1119
Data Float
225
nvoHTR_09_20
inc count (9)
Output (non-polled)
31119
9
Comm Address
SMD_BAS_IP_HTR_09_[0]
AV:1100
Data Float
206
nvoHTR_09_1
inc count (9)
Output (non-polled)
31100
Blr Addr 10
10
Comm Address
SMD_BAS_IP_HTR_10_[0]
AV:1200
Data Float
226
nvoHTR_10_1
inc count (9)
Output (non-polled)
31200
10
Unit Status
SMD_BAS_IP_HTR_10_[1]
AV:1201
Data Float
227
nvoHTR_10_2
inc count (9)
Output (non-polled)
31201
10
Fault Code
SMD_BAS_IP_HTR_10_[2]
AV:1202
Data Float
228
nvoHTR_10_3
inc count (9)
Output (non-polled)
31202
10
Outlet Temp
SMD_BAS_IP_HTR_10_[3]
AV:1203
Data Float
229
nvoHTR_10_4
inc count (9)
Output (non-polled)
31203
10
FFWD Temp
SMD_BAS_IP_HTR_10_[4]
AV:1204
Data Float
230
nvoHTR_10_5
inc count (9)
Output (non-polled)
31204
10
Inlet Temp
SMD_BAS_IP_HTR_10_[5]
AV:1205
Data Float
231
nvoHTR_10_6
inc count (9)
Output (non-polled)
31205
10
Exhaust Temp
SMD_BAS_IP_HTR_10_[6]
AV:1206
Data Float
232
nvoHTR_10_7
inc count (9)
Output (non-polled)
31206
10
Air Temp
SMD_BAS_IP_HTR_10_[7]
AV:1207
Data Float
233
nvoHTR_10_8
inc count (9)
Output (non-polled)
31207
10
Flame Strength
SMD_BAS_IP_HTR_10_[8]
AV:1208
Data Float
234
nvoHTR_10_9
inc count (9)
Output (non-polled)
31208
10
Fire Rate In
SMD_BAS_IP_HTR_10_[9]
AV:1209
Data Float
235
nvoHTR_10_10
inc count (9)
Output (non-polled)
31209
10
Fire Rate Out
SMD_BAS_IP_HTR_10_[10]
AV:1210
Data Float
236
nvoHTR_10_11
inc count (9)
Output (non-polled)
31210
10
Unit Type
SMD_BAS_IP_HTR_10_[11]
AV:1211
Data Float
237
nvoHTR_10_12
inc count (9)
Output (non-polled)
31211
10
Unit Size
SMD_BAS_IP_HTR_10_[12]
AV:1212
Data Float
238
nvoHTR_10_13
inc count (9)
Output (non-polled)
31212
10
Value State
SMD_BAS_IP_HTR_10_[13]
AV:1213
Data Float
239
nvoHTR_10_14
inc count (9)
Output (non-polled)
31213
10
Net Remote Setpt
SMD_BAS_IP_HTR_10_[14]
AV:1214
Data Float
240
nvoHTR_10_15
inc count (9)
Output (non-polled)
31214
10
Run Cycles Upper
SMD_BAS_IP_HTR_10_[15]
AV:1215
Data Float
241
nvoHTR_10_16
inc count (9)
Output (non-polled)
31215
10
Run Cycles Lower
SMD_BAS_IP_HTR_10_[16]
AV:1216
Data Float
242
nvoHTR_10_17
inc count (9)
Output (non-polled)
31216
10
Run Hours Upper
SMD_BAS_IP_HTR_10_[17]
AV:1217
Data Float
243
nvoHTR_10_18
inc count (9)
Output (non-polled)
31217

Table of Contents