4 PROGRAMMING
Next, only the CFW500 frequency converter parameters related to the DeviceNet communication will be
presented.
4.1 SYMBOLS FOR THE PROPERTIES DESCRIPTION
P0105 – 1
ST
/2
ND
RAMP SELECTION
P0220 – LOCAL/REMOTE SELECTION SOURCE
P0221 – SPEED REFERENCE SELECTION – LOCAL SITUATION
P0222 – SPEED REFERENCE SELECTION – REMOTE SITUATION
P0223 – FORWARD/REVERSE SELECTION – L OCAL SITU ATI ON
P0224 – RUN/STOP SELECTION – L OCAL SI TUATION
P0225 – JOG SELECTION – LOCAL SITUATION
P0226 – FORWARD/REVERSE SELECTION – REMOTE SITUATION
P0227 – RUN/STOP SELECTION – REMOTE SITUATION
P0228 – JOG SELECTION – REMOTE SITUATION
These parameters are used in the configuration of the command source for the CFW500 frequency converter
local and remote situations. In order that the device be controlled through the DeviceNet interface, the options
‘CANopen/DeviceNet/Profibus DP’ available in these parameters, must be selected.
The detailed description of these parameters is found in the CFW500 programming manual.
P0313 – COMMUNICATION ERROR ACTION
Range: 0 = Inactive Default: 1
1 = Disable via Run/Stop
2 = Disable via General Enable
3 = Change to Local
4 = Change to Local keeping commands and reference
5 = Causes a Fault
Properties: CFG
Access groups via HMI: NET
It allows the selection of the action to be executed by the device, if it is controlled via network and a
communication error is detected.