P0703 ā BUS OFF RESET
Range: 0 = Manual Default: 0
1 = Automatic
Properties: CFG
Access groups via HMI: NET
It allows programming the inverter behavior when detecting a bus off error at the CAN interface:
Table 4.5: Options for the parameter P0703
If
bus off
occurs, the A134/F234 alarm will be indicated on the HMI,
the action programmed in parameter P0313 will be executed and the
communication will be disabled. In order that the inverter
communicates again through the CAN interface, it will be necessary
to cycle the power of the inverter.
If
bus off
occurs, the communication will be reinitiated automatically
and the error will be ignored. In this case the alarm will not be
indicated on the HMI and the inverter will not execute the action
programmed in P0313.
P0705 ā CAN CONTROLLER STATUS
Range: 0 = Disabled Default: -
1 =
Autobaud
2 = CAN Enabled
3 =
Warning
4 =
Error Passive
5 =
Bus Off
6 = No Bus Power
Properties: RO
Access groups via HMI: NET
It allows identifying if the CAN interface board is properly installed and if the communication presents errors.
Table 4.6: Values for the parameter P0705
Inactive CAN interface. It occurs when the equipment does not have the CAN
CAN controller is trying to detect baud rate of the network (only for DeviceNet
communication protocol).
CAN interface is active and without errors.
CAN controller has reached the
warning
state.
CAN controller has reached the
error passive
state.
CAN controller has reached the
bus off
state.
CAN interface does not have power supply between the pins 1 and 5 of the