5.10 MANUFACTURER SPECIFIC CLASSES
The Manufacturer Specific Classes are used for mapping all CFW500 parameters. These classes allow the user
to read from and write to any parameter through the network. The Manufacturer Specific Classes use DeviceNet
explicit messages. There are separate ranges for each group of parameters, as presented in Table 5.16:
Table 5.16: Manufacturer Specific Classes
Table 5.17: Parameters of the Manufacturer Specific classes
The CFW500 uses only instance 1 for Manufacturer Specific Classes.
In order to access the parameters through the Manufacturer Spe
cific Classes, add the value 100
to the last two digits of any parameter. This new resulting number is known as attribute.
For instance:
Parameter 23: class 64h, instance 1, attribute 123. This path gives access to P0023.
Parameter 100: class 65h, instance 1, attribute 100. This path gives access to P0100.
Parameter 202: class 66h, instance 1, attribute 102. This path gives access to P0202.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com