P0710 ā DEVICENET I/O INSTANCES
Range: 0 = ODVA Basic Speed (2 words) Default: 0
1 = ODVA Extended Speed (2 words)
2 = Manuf.Spec. 2W (2 words)
3 = Manuf.Spec. 3W (3 words)
4 = Manuf.Spec. 4W (4 words)
5 = Manuf.Spec. 5W (5 words)
6 = Manuf.Spec. 6W (6 words)
Properties: CFG, CAN
Access groups via HMI: NET
It allows selecting the
Assembly
class instance for the I/O type communication.
The CFW500 frequency converter has seven setting options. Two of them follow the ODVA
AC/DC Drive Profile.
The other five represent specific CFW500 frequency converter words. The tables presented next describe each
of these control and monitoring words.
If this parameter is changed, it becomes valid only after cycling the power of the product.
0 = Data format for the
ODVA Basic Speed
(2 words) instances:
Called
Basic Speed,
these instances represent the simplest operation interface of a device according to the
AC/DC Device Profile.
The data mapping is showed below.
Monitoring (Input)
70
0
Running1
Faulted
1 -
2 Speed Actual (low byte)
3 Speed Actual (high byte)
Control (Output)
20
0
Fault Reset
Run Fwd
1 -
2 Speed Reference (low byte)
3 Speed Reference (high byte)
1 = Data format for the
ODVA Extended Speed
(2 words) instances:
Called
Extended Speed,
these instances present an equipment operation interface a little bit more refined,
which follows the
AC/DC Device Profile.
The data mapping is showed below.