5
DETAILED PARAMETER DESCRIPTION
Description:
It defines the origin of the Start/Stop command in the REMOTE situation.
When the DIx inputs have the FORWARD/REVERSE function, the HMI keys
|
and
O
will remain inactive
regardless of the value set in P0227.
Table 5.32: Start/Stop Selection REMOTE Situation
P0227 Function
0
HMI
l
and
0
keys
1
Digital input DIx
2
Serial
3
Fieldbus
4
PLC
5
Graphic HMI
|
and
O
key
NOTE!
This parameter can be changed only with the motor stopped.
P0228 - JOG Selection - REMOTE Situation
Adjustable range: 0 to 6 Factory setting: 1
Acesso: Menu Configurations Commands Remote
Description:
It defines the origin of the JOG command in the REMOTE situation.
The speed reference value for JOG is provided by parameter P0122.
LOCAL
REMOTE
COMMANDS COMMANDS
REFERENCE REFERENCE
REFERENCE
(P0221)
REFERENCE
(P0222)
DIRECTION OF ROTATION
(P0223)
DIRECTION OF ROTATION
(P0226)
RUN/STOP
(P0224)
RUN/STOP
(P0227)
JOG
(P0225)
JOG
(P0228)
REFERENCE
LOCAL
(P0220)
LOCAL/REMOTE
SELECTION
REFERENCE
REMOTE
COMMANDS
LOCAL
COMMANDS
REMOTE
Figure 5.23: LOCAL/REMOTE situation block diagram