5
DETAILED PARAMETER DESCRIPTION
The speed reference value for JOG is provided by parameter P0122 (Speed reference for JOG or JOG+).
Table 5.30: Selection of JOG Source LOCAL Situation
P0225
Function
0
Disable
1
HMI
key
2
Digital inputs DI3 to DI10 (P0265 to P0272)
3
Serial
4
Fieldbus
5
PLC
6
Graphic HMI
key
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0226 - Selection of Direction of ROTATION REMOTE Situation
Adjustable range: 0 to 13 Factory setting: 2
Acesso: Menu → Configurations → Commands → Remote
Description:
It defines the origin of the forward/reverse command and the direction used in REMOTE situation.
Table 5.31: Selection of Direction of ROTATION REMOTE Situation
P0226 Function
0
Always forward
1
Always reverse
2
HMI key (Forward default)
3
HMI key (Reverse default)
4
Digital Input DI2 (P0264 = 0)
5
Serial (Forward default)
6
Serial (Reverse default)
7
Fieldbus (Forward default)
8
Fieldbus (Reverse default)
9
AI4 Polarity
10
Forward PLC
11
Reverse PLC
12
Graphic HMI key (Forward)
13
Graphic HMI key (Reverse)
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0227 - Start/Stop Selection REMOTE Situation
Adjustable range: 0 to 5 Factory setting: 0
Acesso: Menu → Configurations → Commands → Remote
MVW3000 | 5-38