EasyManua.ls Logo

WEG MVW3000 - Page 114

WEG MVW3000
264 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
DETAILED PARAMETER DESCRIPTION
The speed reference value for JOG is provided by parameter P0122 (Speed reference for JOG or JOG+).
Table 5.30: Selection of JOG Source LOCAL Situation
P0225
Function
0
Disable
1
HMI
JOG
key
2
Digital inputs DI3 to DI10 (P0265 to P0272)
3
Serial
4
Fieldbus
5
PLC
6
Graphic HMI
JOG
key
NOTE!
This parameter can be changed only with the motor stopped.
P0226 - Selection of Direction of ROTATION REMOTE Situation
Adjustable range: 0 to 13 Factory setting: 2
Acesso: Menu Configurations Commands Remote
Description:
It defines the origin of the forward/reverse command and the direction used in REMOTE situation.
Table 5.31: Selection of Direction of ROTATION REMOTE Situation
P0226 Function
0
Always forward
1
Always reverse
2
HMI key (Forward default)
3
HMI key (Reverse default)
4
Digital Input DI2 (P0264 = 0)
5
Serial (Forward default)
6
Serial (Reverse default)
7
Fieldbus (Forward default)
8
Fieldbus (Reverse default)
9
AI4 Polarity
10
Forward PLC
11
Reverse PLC
12
Graphic HMI key (Forward)
13
Graphic HMI key (Reverse)
NOTE!
This parameter can be changed only with the motor stopped.
P0227 - Start/Stop Selection REMOTE Situation
Adjustable range: 0 to 5 Factory setting: 0
Acesso: Menu Configurations Commands Remote
MVW3000 | 5-38