292903400000/00/09.2022
SQ laser applicator
Parameter Meaning Default
Device information Applicator information: Software version, overall and service counters for the number of labelling
operations, error messages and cylinder cycles
Reset service counter Reset the service counter shown in the device information (only accessible with Service Key)
Cycle sequence Select the type of cyclical operation:
Print/Apply:
The start signal triggers the printing of a label followed by the application of the label to
a product. After completing a cycle, the stamp without label is in the start position.
Apply/Print:
Aseparatesignalstartstheprintingoftherstlabelandthetransfertothestamp.
The start signal triggers the application of the label followed by the printing of the next
label. After completing a cycle, a label is in position on the stamp.
Print/
Apply
Dispensing offset Move the dispensing position in relation to the rear edge of the label.
Thesettingcanalsobemodiedusingthesoftware.Thevaluesfromtheconguration
and software are added together.
0.0 mm
Transfer mode Select the mode of operation: Stamp, Blow Stamp
Wait position Only for mode of operation = Blow and cycle sequence = Apply/Print
Start position: Stamp waits in start position for start signal
End position: Stamp waits in labelling position for start signal
End position
Blow time Only for mode of operation = Blow
Duty cycle (max. 2.5 s) of the blow air to transfer the label
1000 ms
Delayed support air on Delay time (max. 2.5 s) between the start of printing and activation of the support air.
The delay prevents swirling air at the front edge of the label which can lead to errors
during the label transfer
0 ms
Delayed support air off Delay time (max. 2.5 s) between the end of the label feed and the deactivation of the
support air. After-blowing supports the separation of the rear edge of the label from the
carrier to prevent errors and improve the positioning accuracy
270 ms
Start delay Time (max. 2.5 s) between the start signal and the start of the labelling cycle; intended,
e.g. for the use of product sensors on conveyor belts
0 ms
Blocking time
Aftertherststartsignal,allotherstartsignalswithintheblockingtime(max.2.5s)are
ignored; intended, e.g. to debounce the start signal
0 ms
Vacuum monitoring Monitoring of the label transfer by the vacuum sensor On
Label transfer Passive: The stamp waits for the label in front of the dispensing edge.
Active: The stamp is moved to the dispensing edge and collects the label.
Passive
After-blowing After setting down the label, a short puff pulse to clean the suction channel is activated On
Delayed Vacuum
On: The vacuum is turned on after completing the label transport.
O: The vacuum is turned on at the start of the label transport.
Off
Stamp pre-check Achecktoconrmwhetherthestampisemptytakesplacebeforeeveryprinting
process.
On
Time overrun move-
ment
Maximum permissible time for individual cylinder movements. Exceeding the set time
leads to an error message, only accessible with the Service Key
2.0 s
Vacuum switching
threshold
Threshold for evaluating the vacuum at the stamp as adequate for operation, only ac-
cessible with the Service Key
-0.04 bar