1)
Add additives to the fluid on the pressure side of the pump, even
if this is contrary to the recommendations of the additive manufac-
turer.
Use only branded products with corrosion protection inhibitors!
Comply with the chloride content of the top-up water according to
the manufacturer’s instructions! Chloride containing soldering
pastes are not permitted!
Follow the safety data sheets and manufacturer’s instructions!
Salty fluids
CAUTION
Material damage due to salty fluids!
Salty fluids (e.g. carbonates, acetates or formates) are very cor-
rosive and can damage the pump!
Fluid temperatures above 40°C are not permitted for salty fluids!
Use a corrosion inhibitor and constantly check its concentration!
NOTICE
Use other fluids only after approval by WILO SE!
CAUTION
Material damage can occur due to the accumulation of
chemicals!
When changing, refilling or replenishing the fluid with additives,
there is a risk of material damage caused by the accumulation of
chemicals.
Rinse the pump separately and thoroughly. Ensure the old fluid has
been completely removed from the interior of the pump!
Remove pump before change in pressure flushes!
For chemical flushing measures:
Remove the pump from the system for the duration of cleaning!
Drinking water pumps:
WARNING
Health hazard!
Because of the materials used, pumps of the Stratos
MAXO/ -D series are unsuitable for use in applica-
tions involving drinking water or foodstuffs.
The smart-pumps of the Stratos MAXO-Z series are coordinated
specifically for operating conditions in domestic hot water circula-
tion systems through a selection of materials and their design, tak-
ing account of the guidelines of the German Environmental Agency
(Umweltbundesamt):
Drinking water acc. to EC Drinking Water Directive.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Stratos MAXO and is the answer not in the manual?

Wilo Stratos MAXO Specifications

General IconGeneral
Product NameWilo Stratos MAXO
CategoryWater Pump
Control TypeElectronic
DisplayLCD
Temperature Range-10°C to +110°C
Motor TypeEC Motor
Power Supply1~230 V, 50/60 Hz
Voltage230 V
Frequency50/60 Hz
Pump TypeCirculation Pump
ApplicationHeating, Cooling
Energy Efficiency IndexEEI ≤ 0.20
Max Operating Pressure10 bar
Operating ModeConstant Speed
MaterialCast Iron, Stainless Steel
Connection SizeDN 32 to DN 100