Installation and operating instructions Wilo-Stratos MAXO/-D/-Z 41
2. Remove the module cover.
➜Fig.22
Follow the detailed instructions online for further steps!
➜See QR code or www.wilo.com/stratos-maxo/om
6.4 Analogue input (AI1) or (AI2) - purple terminal block
➜Fig.23
Analogue input for following signals:
0–10V
2–10V
0–20mA
4–20mA
PT1000
Dielectric strength: 30VDC/24VAC
The analogue inputs can be used for the following functions:
External setpoint specification
Sensor connection: temperature sensor, differential pressure
sensor, PID sensor
Terminal for supplying active sensors with 24VDC
Maximum current load: 50mA
Analogue input load (0) 4–20mA: ≤300Ω
Load resistance at 0–10V: ≥10kΩ
6.5 Digital input (DI1) or (DI2) - grey terminal block
➜Fig.23
Digital input for potential-free contacts:
Maximum voltage: <30VDC/24VAC
Maximum loop current: <5mA
Operating voltage: 24VDC
Operating loop current: 2mA (per input)
The pump can be controlled with the following functions via ex-
ternal potential-free contacts at the DI1 or DI2 digital inputs:
External OFF
External MAX
External MIN
external MANUAL
External key lock
Heating/cooling switchover
In systems with a high switching frequency (>100 on/off opera-
tions per day); switching on/off takes place via “External OFF”.
6.6 Wilo Net – green terminal block
Wilo Net is a Wilo system bus used for establishing communication
between Wilo products:
Two single pumps as twin-head pump function
Several pumps used with Multi-Flow Adaptation control mode
Gateway and pump
Follow the detailed instructions online for connection.
➜See QR code or www.wilo.com/stratos-maxo/om
6.7 Collective fault signal (SSM) – red terminal block
➜Fig.23
An integrated collective fault signal is applied at the SSM terminals
as a potential-free changeover contact.
Contact load:
Permitted minimum: SELV 12VAC/DC, 10mA
Permitted maximum: 250VAC, 1A, AC1 / 30VDC, 1A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Wilo Stratos MAXO and is the answer not in the manual?

Wilo Stratos MAXO Specifications

General IconGeneral
Product NameWilo Stratos MAXO
CategoryWater Pump
Control TypeElectronic
DisplayLCD
Temperature Range-10°C to +110°C
Motor TypeEC Motor
Power Supply1~230 V, 50/60 Hz
Voltage230 V
Frequency50/60 Hz
Pump TypeCirculation Pump
ApplicationHeating, Cooling
Energy Efficiency IndexEEI ≤ 0.20
Max Operating Pressure10 bar
Operating ModeConstant Speed
MaterialCast Iron, Stainless Steel
Connection SizeDN 32 to DN 100