EasyManua.ls Logo

Wolf COB - Page 41

Wolf COB
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
41
3062547_201507
- Measure the ue gas, CO
2
content, ue gas temperature and soot value and enter
them in the commissioning report (chapter 29).
- Modifying the parameter HG00 has also adjusted the speed for stage 1. For checking
purposes, the boiler must be set to stage 1.
- Switch HG28 burner operating mode from 2 (two-stage) to 1 (single stage).
- Measure the CO
2
content and compare it against the values given in the stage 1
table adjacent.
- If the value is outside the set value, the CO
2
value must be adjusted via the pump
pressure (see chapter 28 "Commissioning without Wolf control accessories").
- Reset HG28 burner operating mode from 1 to 2.
- Terminate the emissions test mode by turning the program selector switch on the
BM programming module to the required operating mode. If emissions test mode
is not reset manually, the appliance switches back to the original operating mode
automatically after 15 minutes.
- Remove the test probe and close the test port.
27. CO
2
check/adjustmentbymatching
the pipe lengths
CO
2
adjustmentby
matching the pipe
lengths
WithcontractorparameterHG00(seechapter19"Contractorlevelparameters"),
theappliancescanbematchedtotheuegassystembychangingthespeed
for both stages.
- The casing must be closed for this setting.
- Remove the cap from the l.h. "ue gas" test port.
- Insert the test probe of the CO
2
measuring instrument into the "ue gas" test port
(approx. 70 mm).
- Turn the program selector switch on BM module to "Emissions test". (Illuminated
signal ring as status indicator ashes yellow.)
- Measure the CO
2
content and compare it against the values given in the Stage 2
table adjacent.
- If required, alter the CO
2
content with parameter HG00.
Completingtheadjustments
- Check the control parameters and match them to the system if necessary.
- Check the condensate drain.
- Instruct the customer in the operation of the boiler, with the aid of the operating
instructions.
- Complete the commissioning report (chapter 29) and hand over the instructions to
the customer.
- Instruct the customer about the need for annual servicing.
- Instruct the customer about energy saving options.
- Refer your customer to section "Information regarding energy efcient operation" in
the operating instructions.
CO
2
check in the lower load
(stage1)
CO
2
setvalue,boilerclosedstage1
13.5 ± 0.3%
AdjustingtheCO
2
valueinthe
upperloadrange(stage2)
(emissionstestmode)
CO
2
setvalue,boilerclosedstage2
13.5 ± 0.3%
HG 00 CO
2
settings
Factory setting: 3
1 2 3 4
5
Lower CO
2
valueHigher CO
2
value

Other manuals for Wolf COB

Related product manuals