EasyManua.ls Logo

Wolf COB - Commissioning Without Wolf Control Accessories (BM)

Wolf COB
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
3062547_201507
28. Commissioning without Wolf control
accessories(BM)
0
I
0
°C
20
40
60
80
100
120
ON/OFF
switch
Heating water
temperature
selector
DHW
temperature
selector
Commissioning
Only qualified personnel must carry out the commissioning and
operationoftheboiler,aswellasinstructtheuser.
- Remove front and top casing.
- Pivot the control unit downwards.
- Insert the oil pressure gauge into the pump's pressure gauge test port.
- Remove the cap from the l.h. "ue gas" test port.
- Insert the test probe of the CO
2
measuring instrument into the "ue gas" test port.
(approx. 70 mm).
- Turn the heating water temperature selector to "Emissions test"
(illuminated signal ring as status indicator ashes yellow.)
- Measure the CO
2
content and compare it against the values given in the stage 2
table adjacent.
- If required, set the CO
2
content with the stage 2 pressure regulating screw using a
4 mm Allen key in accordance with the table.
Turn clockwise - higher CO
2
value
Turn anti-clockwise - lower CO
2
value
CO
2
settingsvia
pump pressure
IfnocontrolaccessoryisconnectedtotheapplianceortheCO
2
setvalueisnot
achievedbymatchingthepipelengths,thesettingismadeviapumppressure
control:
"Inlet air"
test port
"Flue gas"
test port
- Checktheboilerandsystemforleaks.Normaloperatingpressure
whensystemiscold1.5-2.0bar.Preventwaterleaks.
- Check location and seating of the installation.
- Checkthefuellevelintheoiltank.
-
Check all connections and component links for leaks.
-
If tightness cannot be ensured then there is a danger of water damage.
NB
- Fit casing.
- Check that all ue gas accessories have been correctly installed.
- Open the shut-off valves on ow and return.
- Open oil shut-off valves (tank, oil line, lter).
- Switch ON the heating system emergency stop switch.
- Switch ON the system ON/OFF switch on the control unit.
- Remove cap from r.h. test port (inlet air).
- Insert test probe 2 cm.
- Turn DHW temperature selector to 1.
- Turn heating water temperature selector to "Emissions test"
(illuminated signal ring ashes yellow).
- After a pre-purge time of approx. 25 seconds, the pump starts up and opens the
solenoid valve. The supplied fuel oil reaches the nozzle and a ame is established.
- The burner enters a fault state if, during commissioning, the oil pump does not supply
sufcient oil during the pre-purge time. Repeat the burner start by pressing reset.
- Measure temperature and CO
2
in the inlet air and enter the values in the commissioning
report in chapter 24.
- The ue is not gas tight if the CO
2
content > 0.2%; rectify the leak.
- Terminate the emissions test mode by turning the temperature selector back to its
original position.
- If emissions test mode is not reset manually, the appliance switches back to the
original operating mode automatically after 15 minutes.
- Remove the test probe and close the test port. Ensure the cap is seated rmly.
AdjustingtheCO
2
valueinthe
upperloadrange(stage2)
(emissionstestmode)
Vacuum test
connection
Vacuum test
connection
Oil pressure
test connection
Oil pressure
test connection
Pressure regulating
screw, stage 2
Pressure regulating
screw, stage 2
Pump Danfoss
Pump Suntec

Other manuals for Wolf COB

Related product manuals