31. Design information
1)
Marking "x" indicates that all components of the ue are surrounded by combustion air and meet increased requirements for gas
tightness.
2)
For types B23 and B33, the combustion air is drawn from the installation room (open ue combustion equipment).
For type C, the combustion air is drawn through a sealed system from the outside (balanced ue combustion equipment).
Connectiontypes
The following balanced ue or ues with CE-0036-CPD-9169003 certication may be used:
Flue DN 80
Concentric balanced ue DN 80/125
Flue DN 110
Concentric balanced ue (on an external wall) DN 80/125
Flue (exible) DN83, DN110
Concentric balanced ue (on an external wall) DN 110/160
Flue DN 160 (for cascade)
The necessary type plates and certicates are included with the relevant Wolf accessories.
Observe all additional installation instructions included with accessories.
Boiler
type
Appliance type
1), 2)
Operating mode Can be connected to
Open ue Balanced
ue
Moisture-resistant
chimney
Balanced ue
chimney
Balanced ue Certied
balanced ue
Moisture-
resistant ue
COB-
15/20/
29/40
B23, B33, C53,
C33x, C43x,
C53x, C63x,
C83x, C93x
Yes Yes B33, C53, C83x C43x C33x, C53x,
C93x
C63x B23, C53x,
C83x