EasyManua.ls Logo

Wolf COB - Contractor Level Parameters

Wolf COB
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
3062547_201507
19.Contractorlevelparameters
Contractorlevel
Press the r.h. rotary selector to change to control level 2. Turn the r.h. rotary selector
clockwise to select the contractor level and conrm the selection by pressing the r.h.
rotary selector again.
The display shows the code scan.
Heating
contractor
The correct code is set by pressing (display indication ashes) and then turning the r.h.
rotary selector from 0 to 1. After changing the code from 0 to 1, pressing the r.h. rotary
selector again conrms the setting; you are then at the contractor level.
Code scan
code NO
- - - -
Factory setting: 1
Maximum DHW temperature
Parameter A14
65
Factory setting: 65 °C
Setting range: 60 to 80 °C
A14
The maximum DHW temperature is factory-set to 65 °C. If, for commercial reasons,
a higher DHW temperature is required, a maximum temperature of up to 80 °C is
enabled.
If pasteurisation has been activated (BM), the DHW cylinder will be heated to the
selected maximum DHW temperature during the rst cylinder heating of the day.
Take adequate measures to prevent scalding.
Parameter HG22 (maximum boiler water temperature) should be set at
least 5 K higher than the selected maximum DHW temperature.
DHWtemperaturesofover60°Carenotpermissibleinconjunctionwith
aTSstraticationcylinder.
NB
The boiler circuit pump operates constantly if the outside temperature stays below
the selected value. The burner starts and heats the boiler to at least 20 °C if the boiler
water temperature falls below +5 °C.
Note:
Only change the factory setting if you can ensure that the heating system and its
components will not freeze up at low outside temperatures.
Frost protection limit
Parameter A09
2.0
Factory setting: 2 °C
Setting range: -20 to +10 °C
Incorrect operation can lead to system faults.
Please note when adjusting parameter A09 (frost protection / outside
temperature), that frost protection is no longer safeguarded if you set
temperatures lower than 0 °C. This can lead to heating system damage.
NB
A09
The heating circuit pump is switched OFF during cylinder heating with DHWpriority
(0). The boiler energy will then be used exclusively for DHW heating. The burner
shuts down and the heating circuit pump is started as soon as the cylinder has
reached its set temperature. The calorier charge pump runs on in summer operating
mode for the period set in parameter HG19 (calorier charge pump run-on time).
In winter operating mode the calorier charge pump runs on for 2 min. following
successful calorier charging.
The heating circuit pump continues to operate in parallelDHWmode(1). Cylinder
heating ends when the cylinder reaches the set water temperature. The calorier
charge pump runs on in summer operating mode for the period set in parameter
HG19 (calorier charge pump run-on time).
In parallel DHW mode (1), the heating circuit can temporarily be operated
at a higher temperature.
Parallel operation in conjunction with a stratication cylinder is not recommended.
NB
Parallel DHW operation
Parameter A10
A10
Factory setting: 0
Setting range: 0 / 1
0

Other manuals for Wolf COB

Related product manuals