Page #63 background imageLoading...
Page #63 background image
97-0019-01-01 49
Configuring the Freedom SW using the SCP
An overview of the Freedom SW menu structure is shown
below. The SCP displays the Freedom SW basic settings
menu.
Figure 23 Menu Map of the Freedom SW Basic Settings
FSW3012 00: Setup
Mode
Battery
Load
AC In
Inverter
Search Mode
Charger
Force Chg State
Equalize
Desired Mode
Clear Faults Warnings
View Device Info
Basic Settings
Invert
11.8V -88.0A N/A
915W 120V 7A
0V 0A 0Hz
[Enabled]
[Disabled]
[Disabled]
[Disabled]
[Standby]
StatusConfigurable Settings
FSW3012 00: Dev Info
View Fault Log
View Warning Log
View Event Log
FSW3012 00: Basic Settings
Batt Type
Batt Capacity
Max Chg Rate
Charge Cycle
ReCharge Volts
AC In Breaker
Low Batt Cut Out
[Flooded]
[440Ah]
[100%]
[3-Stage]
[12.5V]
[30A]
[11.0V]
[*Enabled] [Disabled]
[*Disabled] [Enabled]
[*Disabled] [Enabled]
[*No Float] [Float] [Bulk]
[Disabled]
[*Standby] [Operating]
[*Flooded] [Gel] [AGM] [Custom]
[*3-Stage] [2StgNoFloat]
Follow procedures on “To select and change a
configurable setting:” on page 43 to change the settings.
FSW Owners Guide.book Page 49 Tuesday, August 7, 2018 9:03 AM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex Freedom SW Series and is the answer not in the manual?

Xantrex Freedom SW Series Specifications

General IconGeneral
Output Voltage120 VAC
Output Frequency60 Hz
AC Transfer SwitchYes
Battery ChargerYes
Input Voltage12V, 24V, 48V DC
ProtectionsOver temperature, overload, short circuit

Related product manuals