FusionServer 1288H V6 Server
Technical White Paper
6 Product Specifications
2022-06-25
68
Category
Specifications
Temperature
Operating temperature: 5°C to 45°C (41°F to 113°F)
(ASHRAE Classes A1 to A4 compliant)
Storage temperature (within three months): 30°C to +60°C
(22°F to 140°F)
Storage temperature (within six months): 15°C to +45°C
(5°F to 113°F)
Storage temperature (within one year): 10°C to +35°C
(14°F to 95°F)
Maximum rate of temperature change: 20°C (36°F) per
hour, 5°C (9°F) per 15 minutes
NOTE
The highest operating temperature varies depending on the server
configuration. For details, see A.3 Operating Temperature Limitations.
Relative humidity (RH,
non-condensing)
Operating humidity: 8% to 90%
Storage humidity (within three months): 8% to 85%
Storage humidity (within six months): 8% to 80%
Storage humidity (within one year): 20% to 75%
Maximum humidity change rate: 20%/h
Air volume
≥ 96 cubic feet per minute (CFM)
Operating altitude
≤ 3050 m (10006.44 ft)
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature decreases by
C (1.8°F) for every increase of 300 m (984.24 ft).
When the server configuration complies with ASHRAE
Class A3 and the altitude is above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C (1.8°F) for
every increase of 175 m (574.14 ft).
When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C (1.8°F) for
every increase of 125 m (410.1 ft).
HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on
gaseous corrosion)
Silver corrosion rate test: 200 Å/month
Particle contaminant
The equipment room environment meets the requirements

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the xFusion Digital Technologies FusionServer 1288H V6 and is the answer not in the manual?

xFusion Digital Technologies FusionServer 1288H V6 Specifications

General IconGeneral
BrandxFusion Digital Technologies
ModelFusionServer 1288H V6
CategoryServer
LanguageEnglish

Related product manuals