PAGE 13
Aquavar IPC Start-Up Genie
Xylem
Input
Motor
Current
Input
Current Limit -
SFA/FLA
Select Motor Type
Select Sleep Frequency Low Limit
Select Filter Type
• None for no lter
• Reactor-Line Load Reactor (KLR Type)
• Dv/Dt (for V1K Type)
• Sinewave for sinewave
(Please refer to the IOM for further
instructions)
Select Yes to Continue to the Application
Setup
Motor Current
5.48A
Example:
SFA is 6.03, FLA is 5.48
Current Limit: 6.03/5.48 = 1.10
Carry over the decimal 2 places to
the right to ensure your Current Limit
percentage = 110%
ForSubmersiblemotorsweinput
SFAandusecurrentlimitat100%
Motor Type
Surface
Sleep Speed
/
Low Limit
30.0Hz
None
Filter Type
Yes