PAGE 9
Aquavar IPC Start-Up Genie
Xylem
Install Jumper wires on:
Terminal 12 and 18
The IPC requires a start command on
terminal 18. To apply a start signal connect
a jumper wire between terminals 18 (DI 18,
parameter 5-10) and 12 (24V dc). A start
command is given to the controller when
terminal 18 is connected to 24V.
Install Transducer cable on:
Brown on terminal 12 (24V)
White on terminal 53 (4-20MA)
Place ground shield between spring clip
and shielded cable.
4. CONTROL WIRING
4.1 SINGLE-PUMP CONTROL WIRING