PAGE 20
Aquavar IPC Start-Up Genie
Xylem
The No Flow Power Calibration Setup
provides the method to program the no ow
power curve in to the controller
- In order to detect a no ow condition for
the various pump(s), the no ow power
curve needs to be programmed in to the
drive
Select Quick Menu
Select 04 Start-Up Genie
Change Setup Selection to Pump Protection.
Select Enable for sleep mode.
Start-Up Genie
Q4
Quick Setup
Q2
Function Setups
Q3
My Personal Menu
Q1
Quick Menus
Setup Selection
Pump Protection
Sleep Mode
Enable
7. NO FLOW POWER CALIBRATION