PAGE 19
Aquavar IPC Start-Up Genie
Xylem
For Multi-Control conguration here are the
parameters that will get autoset:
AutosetConguration
Constant
Pressure
Transducer Max Feedback 300 [unit]
Transducer Type 4-20mA
Feedback 1 Source AI 53
PID Performance Normal
Sleep Mode Enabled
Sleep Frequency 30 Hz
Restart Difference 10 [unit]
No Water/Loss of Prime Fault Enabled
No Water/Loss of Prime Restart Time Enabled
Duty Standby Disabled
Stage Speed 95%
Destage Percentage 80%
Alternation Function On Run Time
Alternation Time 24 Hrs
Pump Exercise Disabled
Acknowledge Auto Set Settings by pressing
the down arrow and cyclying through each of
the four screens.
For further Multi-Pump Setups, Feedback
Setup, Pump Protection Setup, Flow
Compensation, Pipe Fill Setup, please refer
to the IOM.
Select OK to verify Genie is completed.
3/4
Destage Percentage =
80%, Alternation
Function = On Run Time,
Alternation Time = 24
hrs., Pump Exercise =
[unit], No Water/Loss of
Prime fault is enabled,
Restart Time = 10 mins,
Duty Standby = Disabled,
Stage Speed = 95%,
2/4
Constant pressure with
300 [unit], 4-20mA
sensor on AI 53, Sleep
Frequency = 30Hz,
Restart Difference = 10
1/4
Start-Up Genie Complete.
Press [OK] to Exit