Aquavar IPC Start-Up Genie
Xylem
Select 30 Hz for Sleep Frequency, 3 Seconds
for Sleep Delay.
Select 10 for Restart difference.
Select 3 Seconds for Minimum Run Time
Select 10 Seconds for Minimum Sleep Time.
Select 0.0 % for Flow Check Window
Selct 10 Mins for Flow Check Time
Acknowledge that you are enabling sleep
mode based on power consumption and
proceed by pushing the down arrow.
Minimum/Sleep Frequen
18.0Hz
Sleep Delay
3s
0.000
No Flow Restart Difference
Minimum Run Time
10s
Minimum Sleep time
10s
0.00%
Flow Check Window
Flow Check Time
10mins
To enable Sleep Mode
based on power
consumption, No Flow
Power Calibration must
be run on all pumps in the
system. [OK]