CAUTION
Before using the Genie, set DI18 to Stop
(terminal 18 open) to prevent the unit from
starting the motor. Keep terminal 18 open to
avoid an unintended motor rotation. Apply the
Start signal to the controller only when pump
operation is desired.
PREPARE FOR INSTALLATION
WARNING! Installationmustbe
performedbyaqualiedtechnician.
• Suitable Environment – Ensure installation is indoors
and the site temperature range is 0ºC (32ºF) to 40ºC
(104ºF).
• Ensure properly sized safety devices are installed in
the system such as pressure relief valves, compression
tanks, pressure controls, temperature controls and ow
controls.
• Ensure proper guards are installed when the system
has potential to operate at extreme temperatures and/
or pressures.
UNPACK THE UNIT
Remove all packing materials from the product.
Inspect the product to determine if any parts have
been damaged or are missing. Contact your sales
representative if anything is out of order.
PREPARE THE MOUNTING LOCATION
• Ensure adequate supports are utilized to handle the
weight of the system, piping and uid.
• Ensure the suction and discharge pipes are supported
independently by use of pipe hangers near the pump.
• Ensure there is adequate space around the unit to
ensure proper cooling and allow for maintenance and
service.
MOUNT THE UNIT
• Ensure the unit is properly lifted according to the pump
Installation, Operation and Maintenance manual.
• Ensure all ange bolts are adequately torqued.
• For vertically mounted installations with the motor
and controller in the horizontal position, ensure that
adequate support for the motor and controller is
provided.
• Refer to chapter 4 Mechanical Installations in the IM318
Aquavar Intelligent Pump Controller IOM for details of
installations.
INSTALL WIRING
ElectricalHazard.Dangerousvoltage.
Ensure all input power disconnects and
circuit breakers are locked in the off position prior to
installing the input power wiring.
NOTE: External fusing is required for units without a
built in fused disconnect.
ElectricalHazard
Ensure power wiring and fusing is installed according
to NEC/CEC, state, local or municipal codes.
Remove the front cover to gain
access to the power and control
wiring terminals. Connect conduit
runs from the disconnect or service
panel to the drive and route the
power wires through the conduit.
Refer to chapter 5 Electrical
Installation and chapter 10 Technical
Specications in the IM318 Aquavar
Intelligent Pump Controller IOM
(current version) for details on wiring
and routing.