38
ON Running Stop the HYDROVAR by pressing
STOP Manually stopped Start the HYDROVAR by pressing
OFF E-Stop (X3/7-8) is open
To start the HYDROVAR close E-Stop circuit or bridge terminal
X3/7-8
Parameters 02 and 03 for Modes: Controller, Cascade Relay, Cascade Serial, Cascade Synchron
02
02 REQUIRED VAL
Set the desired required value with or
D1 X.XX PSI
The current REQUIRED VALUE and its source (D1 in this example) are displayed.
The available sources are listed below:
D1 internal - required value 1 (set by parameter 0820)
D2 internal - required value 2 (set by parameter 0825)
U1 required value 1 - voltage signal input (Connected to X3/13)
U2 required value 2 - voltage signal input (Connected to X3/15)
I1 required value 1 – current signal input (Connected to X3/18)
I2 required value 2 – current signal input (Connected to X3/23)
03
03 EFF REQ VAL
Effective required value
D1 X.XX PSI
Shows the calculated required value based on ACTUAL VALUE INCREASE (0505), ACTUAL VALUE DE-
CREASE (0510) and LIFT AMOUNT (0330). If the required value is inuenced by an offset signal (SUBMENU
OFFSET [0900]) the current active required value is also shown in this window.
Example: Multi-pump-application with two pumps
REQUIRED VALUE [02]: 75.00 PSI
ACT. VALUE INCREASE [0505]: 10.00 PSI
ACT. VALUE DECREASE [0510]: 5.00 PSI
-> REQ VAL EFF [03]: 80.00 PSI
The second pump will increase system pressure to 80.00 PSI.
c) Parameters 02 and 03 for Active MODE [0105] = Actuator
Frequency XX.X Hz
Display in Mode actuator
STOP X.XX PSI
If parameter MODE [0105] is set to Actuator, the parameter REQUIRED VALUE [02] will change to ACTUAL.
FREQ. and is equivalent to parameter [0830]. This allows the HYDROVAR to run to up to two pre-selected
frequencies to manually control the drive.
02
02 ACTUAT. FRQ.
Set the desired frequency with either or
D1 XX.X Hz
Use this parameter to program the drive to up to 2 set frequencies. Requires programming parameter
0805, 0810, and 0815. To manually set the frequency use parameters ACTUATOR FREQUENCY 1 (0830)
and ACTUATOR FREQUENCY 2 (0835).