10.2 Master / Single Inverter
Each error is shown on the display in plain text and saved in the error memory.
The errors can be reset automatically (depending on the setting in parameter ERROR-RESET [0615]) or manually
in following ways:
• cutting the power supply for > 60 seconds
• pressing and simultaneously for about 5 seconds
• open and close the External ON/OFF (Terminals X3/7-8)
No error-message on the display
Error Probable Cause Measure
no AUTOSTART after Parameter AUTOSTART [08] is Check parameter AUTOSTART [08]
power failure set to “OFF”
No operation when system Pressure higher than the start Check parameter START VALUE [04]
pressure < set pressure value or REGULATION MODE and/or REGULATION MODE [0320]
has been changed to INVERSE.
Error-message on the display
Error Probable Cause Measure
• check connection-terminals of the
OVERCURRENT
Current rise at the output
HYDROVAR
ERROR 11
too high
• check the connection-terminal of
the motor and the motor-cable
• check the windings of the motor
Reset:
The power supply for >60 seconds.
• Automatic Error-reset not possible for this failure!
FAILURE MESSAGES

Other manuals for Xylem hydrovar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem hydrovar and is the answer not in the manual?

Xylem hydrovar Specifications

General IconGeneral
Frequency50/60 Hz
Control typeVariable speed drive
Protection classIP55
Communication protocolsModbus
Relative Humidity5% - 95% (non-condensing)
AltitudeUp to 1000 m without derating
Input voltage200-690 V AC
Storage Temperature-25°C to +70°C (-13°F to 158°F)

Related product manuals