EasyManuals Logo

Xylem hydrovar Instruction Manual

Xylem hydrovar
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
72
S
S
• Incoming pressure or minimum level
too low
LACK OF WATER
Low water contact • Bridge X3/11-12, if there is no ext.
ERROR 21
(X3/11-12) is opened low water protection
(only active if motor is running) • Adjust Parameter DELAY TIME [0610]
if the failure happens only for a
short time
Reset: Automatically if low water contact (X3/11-12) is closed!
Dened value of parameter • Check booster unit, adjust
MIN. THRESHOLD MIN.THRESHOLD [0605] was parameter DELAY TIME [0610]
ERROR 22 not reached during the • Parameter ERROR RESET [0615] set
preselected DELAY-TIME [0610] to ON, to enable 5 restarts
Sensor signal on terminals
• ACTUAL VALUE signal (pressure
FAILURE SENSOR 1
X3/2 <4mA
transducer) faulty
Active Sensor:
• Poor connection
ACT. VAL. SENSOR 1
WARNING (20 sec.)-> ERROR
• Sensor or cable fault
ERROR 23
Non-active sensor: WARNING
• check conguration of the sensors
in submenu SENSORS [0400]
Sensor signal on terminals
• ACTUAL VALUE signal (pressure
FAILURE SENSOR 2
X3/2 <4mA
transducer) faulty
Active Sensor:
• Poor connection
ACT. VAL. SENSOR 2
WARNING (20 sec.)-> ERROR
• Sensor or cable fault
ERROR 24
Non-active sensor: WARNING
• check conguration of the sensors
in submenu SENSORS [0400]
Current signal input of required
• Check external analogue signal on
SETPOINT 1 I<4mA
values is active, but no signal
terminals X3/17-18
4-20mA is connected
• Check conguration of the required
SETPOINT 1 I<4mA
WARNING (20 sec.)-> ERROR
values in Submenu REQUIRED
ERROR 25
VALUES [0800]
Current signal input of required
• Check external analogue signal on
SETPOINT 2 I<4mA
values is active, but no signal
terminals X3/22-23
4-20mA is connected
• Check conguration of the required
SETPOINT 2 I<4mA
WARNING (20 sec.)-> ERROR
values in Submenu REQUIRED
ERROR 26
VALUES [0800]
• Cut off power supply for > 60 seconds.
Reset:
• Manual reset by closing external ON/OFF (Terminals X3/7-8)
• Manual reset by pressing and simultaneously for about 5 seconds
• Auto-reset possible if ERROR-RESET [0615] is set to ON
FAILURE MESSAGES

Other manuals for Xylem hydrovar

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xylem hydrovar and is the answer not in the manual?

Xylem hydrovar Specifications

General IconGeneral
Frequency50/60 Hz
Control typeVariable speed drive
Protection classIP55
Communication protocolsModbus
Relative Humidity5% - 95% (non-condensing)
AltitudeUp to 1000 m without derating
Input voltage200-690 V AC
Storage Temperature-25°C to +70°C (-13°F to 158°F)

Related product manuals