EasyManua.ls Logo

YASKAWA 1000 Series

YASKAWA 1000 Series
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Input Assemblies (Drive Produces)
YASKAWA ELECTRIC SIEP C730600 43B 1000-Series Option SI-N3 Technical Manual 53
Enhanced Speed Status, Dynamic (Vendor Specific Yaskawa Electric (YE) Assy) -
155 (0x9B)
Output Instance Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
155
0 FAULT ALARM READY
Speed
Agree
Reset
REV
Running
ZSP Running
1
Multi-
Function
Photocoupler 2
Multi-
Function
Photocoupler 1
Multi-
Function
Digital
Output
LOCAL /
REMOTE
Function
Code
High Bit
Function
Code
Low Bit
Uv oPE
2 Output Frequency (Low Byte)
3 Output Frequency (High Byte)
4 Register Number (Low Byte)
5 Register Number (High Byte)
6 Register Data (Low Byte)
7 Register Data (High Byte)
Parameter Data
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
Reset
0: No Reset
1: Reset
Speed Agree
Speed Agree
0: No Speed Agree
1: Actual speed at speed reference
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
oPE
oPE Fault
0: No oPExx Fault
1: oPExx
Uv
Undervoltage
0: No Undervoltage
1: Undervoltage
Function Code MEMOBUS/Modbus Function Code Refer to Function Code Decode Table on page 29
LOCAL/REMOTE
Status of Run command from Network
0: Run command is not from network
1: Run command is from network
Multi-Function Digital Output
Terminal M1/M2
0: Terminal M1/M2 OFF
1: Terminal M1/M2 ON
Multi-Function Photocoupler 1
Terminal P1
0: Terminal P1 OFF
1: Terminal P1 ON

Other manuals for YASKAWA 1000 Series