EasyManua.ls Logo

YASKAWA CIMR-V7AM

YASKAWA CIMR-V7AM
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation 1-2
Installation Check Sheet
The following is a quick reference check list to install and configure the V7 EtherNet/IP Option Kit. Make a copy of this page and check-off
; each item as it is completed. For detailed information please refer to the detailed sections that follow.
1. Unpack the V7 EtherNet/IP Option Kit and verify that all components are present and undamaged.
2. Connect power to the drive and verify that it runs normally.
Refer to the V7 Technical Manual for information on how to set-up a drive.
4. Install the V7 EtherNet/IP Option Kit on the drive.
5. Connect the V7 EtherNet/IP Option Kit to the EtherNet/IP communication network.
6. Apply power to the drive and check diagnostic and normal operation LED status.
7. Configure the PC for a network connection.
8. Configure the EtherNet/IP Option Kit.
9. Finish the V7 EtherNet/IP Option Kit Installation:
Refer to the documentation included with the EtherNet/IP configuration utility supplied with the EtherNet/IP Master controller.
Verify that the drive appears on the EtherNet/IP network at the correct IP address, Subnet Mask, gateway and server.
When using this kit, it is strongly recommended that no connections be made to the V7 Drive's DC Bus terminals
(+1 and -) on models CIMR-V7AMxxxx, where xxxx is 25P5, 27P5, 45P5, or 47P5. A (+1 to +2) connection for a DC
reactor is allowed.
Note: It is strongly recommended that shielded CAT-5 cable be used. Verify that the shield is continuous to the drive
and that it is grounded only at the drive end.
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.
WAR NIN G!
CAUTION

Related product manuals