5-42
Torque Limits: L7
User constants for torque limits are shown in the following table.
Note The forward torque limit is the limit value when the analog input signal generates forward torque. This torque limit setting is enabled even when the
analog input signal generates forward torque while the motor is operating (regeneration).
* The factory setting will change when the control method is changed.
L6-04
Overtorque/Under-
torque
detection selection 2 Multi-function output for over-
torque detection 1 is output to
multi-function contact output
when overtorque detection 1
NO or overtorque detection 1
NC is selected. Multi-function
output for overtorque detection
2 is output to multi-function
contact output when overtorque
detection 2 NO or overtorque
detection 2 NC is selected.
0 to 8 0 No A A 553H
Torq Det 2 Sel
L6-05
Overtorque/Under-
torque
detection level 2
0 to
300
150% No A A 554H
Torq Det 2 Lvl
L6-06
Overtorque/Under-
torque
detection time 2
0.0 to
10.0
0.1 s No A A 555H
Torq Det 2 Time
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control
Methods
MEMO-
BUS
Register
Open-
loop
Vector
Flux
Vector
Display
L7-01
Forward drive
torque limit
Sets the torque limit value as a percentage
of the motor rated torque.
Four individual regions can be set.
0 to
300
100%
*
No A A 560H
Torq Limit Fwd
L7-02
Reverse drive
torque limit
0 to
300
100%
*
No A A 561H
Torq Limit Rev
L7-03
Forward
regenerative
torque limit
0.0 to
100.0
0.5%
*
No A A 562H
Torq Lmt Fwd
Rgn
L7-04
Reverse
regenerative
torque limit
0.0 to
100.0
0.5%
*
No A A 563H
Torq Lmt Rev
Rgn
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
Output frequency
Accelerates to
lower limit
Same
frequency
Reference
frequency reset
* The frequency matching signal turns on when the motor
is not accelerating/decelerating while the Run Command is on.
Lower limit
Forward
operation/stop
UP command
DOWN
command
Frequency
matching signal*
Power supply
Upper limit
On
On
On
On
On On
d4-01=1
d4-01=0