6-4
Run Command
This section explains input methods for the Run Command.
Selecting the Run Command Source
Set constant b1-02 to select the source for the Run Command.
Related Constants
Performing Operations Using a Digital Operator
When b1-02 is set to 0, you can perform Inverter operations using the Digital Operator keys (RUN, STOP,
JOG, and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes.
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, you can perform Inverter operations using the control circuit terminals.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
b1-02
Operation method
selection
Set the Run Command input
method.
0: Digital Operator
1: Control circuit terminal
(sequence input)
2: MEMOBUS communica-
tions
3: PLC
0 to 3 3 No Q Q 1A1H
Run Source