5-24
PLC Constants: F
The following settings are made with the PLC constants (F constants)
PLC: F8
User constants for PLC are shown in the following table.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
F8-06
Control response 1
selection
Sets the number of the monitor
item to be control response 1.
(U1-)
1 to 99 9 No A A 405H
ControlResponse1
F8-07
Control response 2
selection
Sets the number of the monitor
item to be control response 2.
(U1-)
1 to 99 90 No A A 406H
ControlResponse2
F8-08
Control response 3
selection
Sets the number of the monitor
item to be control response 3
(U1-)
1 to 99 43 No A A 407H
ControlResponse 3
F8-09
Control response 4
selection
Sets the number of the monitor
item to be control response 4.
(U1-)
1 to 99 54 No A A 408H
ControlResponse4
F8-10
Torque reference/
torque limit selection
from PLC
0: Torque reference/torque
limit from PLC disabled.
1: Torque reference/torque
limit from PLC enabled.
0 or 1 0 No A A 409H
Torq Ref/Lmt Sel
F8-11
External-
magnetic-flux
reference selection
0: Disabled.
1: Enabled.
0 or 1 0 No No A 40AH
Ext-Mag-flux Sel
F8-12
ASR proportional gain
selection
0: Disabled.
1: Enabled.
0 or 1 1 No No A 40BH
ASR P Gain Sel
F8-13
Torque limit selection
(FWD)
0: Disabled.
1: Enabled.
0 or 1 1 No A A 40CH
Torque limit Sel
F8-14
Torque limit selection
(REV)
0: Disabled.
1: Enabled.
0 or 1 1 No A A 40DH
Torque limit Sel
F8-15
Speed limit selection
0: Disabled.
1: Enabled.
0 or 1 1 No No A 40EH
Speed limit Sel