EasyManua.ls Logo

YASKAWA FSDrive-MV1S - Stopping Methods; Selecting the Stopping Method When a Stop Command Is Sent

YASKAWA FSDrive-MV1S
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Stopping Methods
6-5
Stopping Methods
This section explains methods of stopping the Inverter.
Selecting the Stopping Method when a Stop Command is Sent
There are two methods of stopping the Inverter when a Stop Command is sent:
Deceleration to stop
Coast to stop
Set constant b1-03 to select the Inverter stopping method.
Related Constants
* The factory setting will change when the control method is changed.
Constant
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control
Methods
MEMOBUS
Register
Open-
loop
Vector
Flux
Vector
Display
b1-03
Stopping method
selection
Used to set the stopping
method used when a Stop Com-
mand is input.
0: Deceleration to stop
1: Coast to stop
0 or 1 1 No Q Q 1A2H
Stopping Method
b1-05
Operation selection for
setting E1-09 or less
Used to set the method of
operation when the frequency
reference input is less than the
minimum output frequency
(E1-09).
0: Run at frequency reference
(E1-09 not effective).
1: STOP (Frequencies below
E1-09 in the coast to stop
state.)
2: Run at min. frequency.
(E1-09)
3: Run at zero-speed (Frequen-
cies below E1-09 are zero)
0 to 3 1* No No A 1A4H
Zero-Speed Oper
b2-01
Zero-speed level (DC
injection braking
starting frequency)
Used to set the frequency
which starts DC injection brak-
ing in 1% units when decelera-
tion to stop is selected.
When b2-01 is less than E1-09,
E1-09 becomes the DC injec-
tion braking starting frequency.
0.00 to
10.00
0.50%
*
No A A 1B0H
DCInj Start Freq
b2-02
DC injection braking
current
Sets the DC injection braking
current as a percentage of the
Inverter rated current.
0 to
100
50% No A No 1B1H
DCInj Current
b2-03
DC injection braking
time at start
Used to set the time to perform
DC injection braking at start in
units of 1 second.
Used to stop coasting motor
and restart it. When the set
value is 0, DC injection braking
at start is not performed.
0.00
to
10.00
0.00
s
No A A 1B2H
DCInj Time@Start
b2-04
DC injection braking
time at stop
Used to set the time to perform
DC injection braking at stop in
units of 1 second.
Used to prevent coasting after
the Stop Command is input.
When the set value is 0.00, DC
injection braking at stop is not
performed.
0.00
to
10.00
0.50
s
No A A 1B3H
DCInj Time@Stop

Table of Contents

Related product manuals