9-2
FSDrive-MV1S Standard Specifications
Specifications by Model
The specifications of 3 kV class models and 6 kV class models are listed below.
All models from 3 kV class 200 kVA to 6 kV class 6000 kVA have the same electric specifications and control
specifications.
3 kV Class Models
* 1. Maximum applicable capacity of Yaskawa’s 4-pole standard motors
* 2. An uninterruptible input power supply unit (optional) for the control power supply is required to use the restart function for momentary power loss.
Table 9.1 3 kV Class FSDrive-MV1S Standard Specifications
Model CIMR-MV1SA
132 200 315 450 630 900 13C 18C 25C
Max. Applicable Motor Capacity (kW)
*1
132 200 315 450 630 900 1250 1800 2500
Output Rating
Nominal Capacity (KVA) 200 285 400 570 800 1150 1500 2300 3000
Rated Output Current (A)
35
(30)
50
(45)
70
(60)
100
(85)
140
(120)
200
(170)
260
(230)
400
(350)
520
(440)
Rated Output Voltage (V) Three-phase 3000/3300 V (sine wave)
Max. Output Frequency 50/60 Hz (up to 120 Hz)
Power Supply
Main Circuit (Input Voltage) Three-phase 3000/3300 V ±10%
Control Circuit
Three-phase 200/220 V, 380 V, 400/440 V ±10%
50/60 Hz ±5%
Inverter Efficiency Approx. 97% (at motor rated speed and 100% load)
Inverter Power Factor 0.95 min. (at motor rated speed and 100% load)
Cooling Method Forced air-cooling method
Control Specifi-
cations
Control Method Open-loop vector control, flux vector control
Main Circuit Voltage type series multiplex
Frequency Control Range 0.01 to 120 Hz
Frequency Control Accuracy ±0.5%
Analog Input Resolution 0.03 Hz
Overload Capacity
120% for 60 seconds (when used with above-mentioned current in
parentheses)
Acceleration/Deceleration Time 0.1 to 6,000 seconds
Main Control Functions
Restart after momentary power loss
*2
, torque limit, coasting to a
stop, jump frequencies, S-curve acceleration/deceleration, multi-
step speed control, KEB function, etc.
Protective Functions
Overcurrent, overvoltage, undervoltage, output ground fault, output
open-phase, overload, motor overheat, etc.
Communications Functions MODBUS, etc.
Maintainability
Control Panel
Status display, fault display, setting/reading of commands and con-
stants
Main Circuit Module configuration
Environmental
Specifications
Enclosure IP 40
Ambient Temperature and Humidity -5 to +40°C, 85%RH max. (with no condensation)
Storage Temperature 0 to +50°C
Atmosphere
General environmental conditions (free from dust or corrosive gas),
altitude: 1,000 m max.
General Specifi-
cations
Paint Color Internal and external surfaces painted in Munsell 5Y/7/1 semiglossy
Applicable Standards JIS, JEC, JEM, Electric Facility Technical Reference